Generator Size Calculator

Power

Starting watts decide the generator, not running watts.

Interactive Tool
Live Calculation

Generator Size Calculator

Recommended running = running watts x (1 + headroom); kVA = running watts / power factor / 1000.

W
W
W
W
%
%
Evaluated Formula:Recommended running = running watts x (1 + headroom); kVA = running watts / power factor / 1000.
Guidance:
Start the largest motor first, then add the rest. Surge watts are not simply the sum of every appliance starting at once.
A conventional generator must cover the surge; an inverter generator may handle motor starting differently. Check the product surge rating and duration.
Power factor converts watts to volt-amperes. A 0.8 power factor means 4,000 W needs about 5 kVA of generator capacity.
Recommended running watts
4,200 W

Calculated instantly

Surge to cover6,000 W
Generator kVA5.25 kVA
Spare capacity at surge2,500 W

Embed this calculator

Put this calculator on your own site with the snippet below. The frame contains the tool only, reports its own height, and carries a visible link back to the full page. Embedding is free; keep the attribution link as it is, and do not wrap the frame in a way that hides it.

Preparing the embed code for this page...

What This Calculator Does

The Generator Size Calculator takes the running and starting watts of the loads you want to back up, adds headroom, and reports the generator size to shop for in watts and kVA. It is a load-planning tool, not a substitute for a transfer switch and a licensed electrical design.

How It Works

Running watts are summed across everything that will operate at once. Headroom is added because generators are rated at sea level under standard conditions and should not run at their limit. The larger of the surge watts and the recommended running watts becomes the starting requirement. kVA is running watts divided by power factor and 1,000, because generators are often sold in volt-amperes rather than watts.

Example

A backup panel with 3,500 running watts and a 6,000 W well pump surge, plus 20 percent headroom, needs 4,200 running watts. The surge to cover is max(6,000, 4,200) = 6,000 W. At a 0.8 power factor the generator is 4,200 / 0.8 / 1000 = 5.25 kVA.

Formula

Recommended running
running watts x (1 + headroom)
Surge to cover
max(surge watts, recommended running)
kVA
running watts / power factor / 1000
Spare surge capacity
surge to cover - running watts

Reading the Results

Recommended running watts

The continuous load plus headroom. A generator run near its rating for hours is loud, inefficient, and short-lived.

Surge to cover

The largest short-term demand, usually a motor starting. If the generator cannot supply it, the motor stalls or the breaker trips.

Generator kVA

The volt-ampere rating to compare with generator labels. Watts and volt-amperes are only equal at a power factor of 1.

Sources and References

  • NFPA 70 National Electrical Code - Article 702, Optional Standby Systems

    Installation requirements for standby power

    Covers transfer equipment and the separation of utility and generator supply. Local amendments apply.

  • Portable Generator Manufacturers Association - sizing guidance

    Running versus starting watts

    Industry guidance on motor starting and generator load planning.

References identify the method or data behind this calculator. Where a standard or tariff changes, the current edition applies, and the assumptions stated above take precedence over a remembered figure.

Frequently Asked Questions

What is the difference between running watts and starting watts?

Running watts are the continuous draw once a device is operating. Starting watts, also called surge watts, are the brief higher draw when a motor starts. Refrigerators, well pumps, furnaces, and air conditioners can draw two to three times their running watts for a few seconds.

Should I add up the starting watts of every appliance?

No. Start the largest motor first, then let it run before starting the next. The generator only has to cover the surge of the last motor plus the running load of everything already on. Adding every surge together over-sizes the generator and wastes fuel.

Do I need a transfer switch?

Yes for a permanently connected generator. A transfer switch prevents backfeeding the utility, which can injure line workers and damage equipment. Portable generators should use a properly rated inlet and interlock, never a suicide cord.

Why is the generator rating in kVA instead of watts?

Alternators are limited by current and voltage, which gives volt-amperes. Real power in watts depends on the power factor of the load. A 5 kVA generator at 0.8 power factor delivers about 4 kW; resistive loads use the full ratio, motors do not.

Does altitude or temperature affect generator capacity?

Yes. Engine-driven generators lose output at high altitude and in high ambient temperatures, and the manufacturer derating chart should be applied. A unit rated at sea level may not carry the same load at 8,000 ft or in a heatwave.