Skip to main content

Voltage Drop Calculator

Electrical

What arrives at the far end of the cable.

Interactive Tool
Live Calculation

Voltage Drop Calculator

Vdrop = I × (2 × ρ × L / A), with L as the one-way length

V
V
A
A
m
m
mm²
mm²
Ω·mm²/m
Ω·mm²/m
Evaluated Formula:Vdrop = I × (2 × ρ × L / A), with L as the one-way length
Guidance:
The factor of two accounts for both conductors: the current travels out and back.
Copper is about 0.0175 Ω·mm²/m at 20 °C; aluminium is about 0.0282. Resistance rises as conductors heat.
A 3% branch-circuit drop and 5% total drop are common design limits, but local wiring regulations govern.
Voltage drop
5.25 V

Calculated instantly

Drop as a percentage of supply2.28 %
Voltage at the load224.75 V
Power lost in the cable105 W

Embed this calculator

Put this calculator on your own site with the snippet below. The frame contains the tool only, reports its own height, and carries a visible link back to the full page. Embedding is free; keep the attribution link as it is, and do not wrap the frame in a way that hides it.

Preparing the embed code for this page...

What This Calculator Does

The Voltage Drop Calculator works out how many volts are lost in a cable run and what voltage remains at the load. It models the out-and-back loop resistance of a two-wire circuit using conductor length, cross-section, and resistivity.

How It Works

Resistance of a conductor is resistivity times length divided by cross-sectional area. Because the return conductor carries the same current, the loop resistance doubles. Multiplying by current gives the volts lost, and subtracting from the supply gives the voltage at the load. The lost power is current squared times loop resistance.

Example

A 20 A load 30 m from a 230 V supply, wired in 4 mm² copper, has a loop resistance of 2 × 0.0175 × 30 / 4 = 0.2625 Ω. The drop is 5.25 V, or 2.28%, leaving 224.75 V at the load and wasting 105 W as heat in the cable.

Formula

Loop resistance
R = 2 × ρ × L / A
Voltage drop
Vdrop = I × R
Load voltage
Vload = Vsupply − Vdrop
Cable power loss
Ploss = I² × R

Reading the Results

Voltage drop

The volts lost between the supply and the load. It is proportional to current, length, and resistivity, and inversely proportional to conductor area.

Voltage at the load

What the equipment actually receives. Motors and compressors are sensitive to low voltage, especially during start-up when current briefly rises.

Sources and References

  • IEC 60364-5-52 — Wiring systems

    Selection and erection of wiring systems, including voltage drop

    The international installation standard that sets voltage-drop guidance for fixed wiring.

  • NFPA 70 — National Electrical Code, 210.19(A) Informational Note

    Branch-circuit and total voltage drop recommendations

    Suggests keeping branch-circuit drop to 3% and total to 5% for reasonable efficiency.

  • IEEE Std 141 — Recommended Practice for Electric Power Distribution

    Voltage-drop calculation methods

    Covers the resistive and reactive components; this calculator handles the resistive part.

References identify the method or data behind this calculator. Where a standard or tariff changes, the current edition applies, and the assumptions stated above take precedence over a remembered figure.

Frequently Asked Questions

Why does the formula use twice the cable length?

Current flows to the load along one conductor and returns along another, so the total conductor length in the circuit is twice the one-way distance. Both lengths contribute resistance.

What is an acceptable voltage drop?

Common design guidance is up to 3% on a branch circuit and 5% overall, but the figure that matters is the equipment tolerance and your local wiring regulations. Some installations require tighter limits.

Does this account for power factor?

No. It assumes a resistive load at unity power factor. For motors and other inductive loads, the resistive drop is combined with a reactive component, which can change the answer significantly.

Why does my cable get warm?

The power lost in the conductor becomes heat. A 105 W loss in the example is a real heating effect, and bundling cables or insulating them reduces how easily that heat escapes, which is why derating factors exist.